Liquid-Line Subcooling to Prevent Flash Gas

How much subcooling a system needs to keep the liquid line from flashing.

Run the calculator

Example

You enter

You get

Details, formula, and sources

dP_lift = 0.43 x lift (R-410A liquid), dP_total = dP_lift + friction, required_subcool = dP_total / P-T slope (~5 psi/degF R-410A). Techs credit only the friction and forget the vertical-lift static column that dominates on a tall riser. A design aid, not a commissioning measurement.

dP_lift = static_gradient x vertical_lift_ft (0.43 psi/ft R-410A liquid); dP_total = dP_lift + friction_dp_psi; required_subcool = dP_total / pt_slope (about 5 psi/degF R-410A near condensing).

ASHRAE Refrigeration Handbook / refrigerant piping guides liquid-line subcooling to prevent flash gas, by name.

The flash-gas relations are standard refrigerant-piping design practice; the manufacturer data and the actual refrigerant govern the commissioning.

Estimate. AHJ and licensed professional govern.

Field names used by the API: vertical_lift_ft, friction_dp_psi, static_gradient, pt_slope, dp_lift_psi, dp_total_psi, required_subcool_f

Related tools