Backflow Assembly Test Pass Criteria

Pass/fail per assembly type with the governing field-test criterion.

Run the calculator

Example

You enter

You get

Checked against published worked examples from: USC FCCCHR Manual / AWWA C511.

Details, formula, and sources

ScopeRP relief opens at >= 2 psid and below the #1 check, the #1 check >= 5 psid, and the #2 check tight; DC each check >= 1 psid. Per the USC FCCCHR Manual and AWWA C511.

Formula or tableRP pass: #1 check >= 5 psid AND above the relief opening point, AND relief opens at >= 2 psid, AND #2 check tight >= 1 psid. DC pass: each check holds >= 1 psid tight.

Source and editionUSC FCCCHR Manual of Cross-Connection Control, 10th edition (field test procedures), and AWWA C511, by name.

Free accessUSC FCCCHR / AWWA published; the tester-procedure thresholds are public. The certified tester and water purveyor govern.

What governsEstimate. Operator of record and primacy agency govern.

API field namesassembly_type, check1_psid, relief_open_psid, check2_psi, buffer_psid