Brick Veneer Weep-Hole Count (IRC R703.8.6)

Weep holes to drain the veneer air space at each through-wall flashing line: weeps per line = ceil(wall length in / max spacing) + 1, so both ends get a weep. IRC R703.8.6 and TMS 402 cap the spacing at 33 in on center (a common tighter spec is 24 in), at least 3/16 in diameter, immediately above the flashing. A 30 ft wall at 33 in is 12 weeps per line; the base course plus every shelf angle and lintel flashing above openings each need their own line. The weeps must sit directly on the flashing over a clear, un-mortar-clogged air space; the AHJ-adopted code and the wall detail govern. Distinct from the veneer ANCHOR count (brick-veneer-anchor-spacing).

Run the calculator

Formula and source

weeps_per_line = ceil(wall_length_ft x 12 / max_spacing_in) + 1; total_weeps = weeps_per_line x round(flashing_lines).

IRC R703.8.6 and TMS 402 masonry-veneer weep-hole provisions, by name; the spacing cap and detail come from the adopted code.

Audience

This tile is built for trades and the adjacent professions in the Carpentry and Construction group. The interactive calculator runs entirely in your browser. No account, no fee, no advertising, no tracking.

Related tools

Posture

Rough Logic answers the math question the working professional asks on the job. The site is a calm, fast, ad-free, account-free, ever-free reference. It does not interpret code. It does not replace the licensed professional. It does not store your inputs. The Authority Having Jurisdiction governs all installations and inspections.