Buck-Boost Transformer Sizing (Single-Phase)
The autotransformer (buck-boost) kVA to correct a line voltage up or down for a load.
Example
You enter
- Supply (line) voltage (V) 208
- Desired (load) voltage (V) 230
- Load current (A) 50
You get
- Boost v 22
- Full load (kVA, reference) 11.5
- Autotransformer rating (kVA) 1.1
Details, formula, and sources
Boost/buck = desired minus supply voltage, and the unit is rated only for that boost times the load current, a fraction of the full load kVA (208 V to 230 V at 50 A -> a 1.10 kVA unit supports an 11.5 kVA load). Sizing a buck-boost by the full load kVA grossly oversizes it. NEC Article 450; the buck-boost selection, connection, and overcurrent protection are the manufacturer's and the AHJ's.
boost_v = desired_v - supply_v; load_kva = desired_v x load_a / 1000; xfmr_kva = abs(boost_v) x load_a / 1000; ratio% = xfmr_kva / load_kva x 100. The autotransformer is rated for the boost/buck voltage times the load current, a fraction of the full load kVA.
Single-phase buck-boost (autotransformer) sizing. NEC 2023 Article 450 (transformers); the autotransformer connection per the manufacturer.
NEC is free to read at nfpa.org/freeaccess. Buck-boost selection, the connection diagram, taps, and overcurrent protection are the manufacturer's and the AHJ's; this sizes the required kVA only.
Estimate. AHJ and licensed electrician govern. Verify against the NEC edition adopted in your jurisdiction.
Field names used by the API: supply_v, desired_v, load_a, boost_v, load_kva, xfmr_kva
- Autotransformer rating rated for the boost/buck voltage (desired minus supply) times the load current, not the full load kVAmanufacturer buck-boost connection tables
- Connection and protection the catalog unit, tap connection, and overcurrent protection are manufacturer- and AHJ-governed, not selected hereNEC Article 450; manufacturer