Combustion Air

Required combustion air opening from BTU input and room volume.

Run the calculator

Example

You enter

You get

Checked against published worked examples from: ICC.

Details, formula, and sources

Formula or tableRequired combustion-air opening per IFGC 2027 §304 (standard method): 1 sq inch per 4000 BTU/hr for outdoor air (two openings), and the larger 1 sq inch per 1000 BTU/hr for indoor communicating air.

Source and editionIFGC 2027 (International Fuel Gas Code) / NFPA 54. §304.

Free accessFree read-only access at codes.iccsafe.org.

What governsEstimate. AHJ and licensed mechanical contractor govern. ACCA Manual J / D / S supersede rules of thumb.

API field namesbtu_input, room_volume_ft3, required_volume_ft3, opening_outdoor_in2, opening_indoor_in2, adequate_by_volume