Auxiliary Condensate Drain Pan (IRC M1411.3.1)

The overflow protection behind the primary drain, and it turns on one misread sentence: the auxiliary pan shall be not less than 3 in larger than the unit or coil in WIDTH AND LENGTH -- 3 in on the OVERALL dimension, not 3 in per side. A 21 in air handler wants a 24 in pan, not 27. Read it the generous way and you buy a bigger pan than the code asks for in an attic where space is not free; read it the other way and you fail. Plus the 1.5 in minimum depth, and the choice among the four methods the section allows -- only TWO of which involve a pan at all, the others relying on an overflow line above the primary connection or a UL 508 shutoff device, which is often the practical answer in a tight space. Whether any of it applies (damage may occur from overflow) is the prior question.

Run the calculator

Formula and source

required pan width = unit or coil width + 3 in; required pan length = unit or coil length + 3 in; minimum pan depth 1.5 in. The 3 in applies to the OVERALL dimension, not to each side, so the per-side misreading would demand width + 6 and length + 6.

IRC M1411.3.1 auxiliary and secondary drain systems, with its four permitted methods and the auxiliary pan dimensions.

Audience

This tile is built for hvac and the adjacent professions in the HVAC group. The interactive calculator runs entirely in your browser. No account, no fee, no advertising, no tracking.

Related tools

Posture

Rough Logic answers the math question the working professional asks on the job. The site is a calm, fast, ad-free, account-free, ever-free reference. It does not interpret code. It does not replace the licensed professional. It does not store your inputs. The Authority Having Jurisdiction governs all installations and inspections.