Containment Air Balance

Required net negative CFM via Q = 2610 * A * sqrt(delta_P) and recommended NAM count.

Run the calculator

Example

You enter

You get

Details, formula, and sources

Orifice flow Q = 2610 × A × sqrt(ΔP) (cfm; A in ft², ΔP in inches WC). Leakage area is entered in in² and converted to ft² (/144). Recommended NAM count = required_negative_flow / per-NAM rated CFM.

Classical orifice-flow theory; constant 2610 from ASHRAE Fundamentals derivation. IICRC S520-2024 §12 for containment guidance.

Orifice-flow derivations free in published engineering texts.

Estimate. AHJ and licensed professional govern.

Field names used by the API: target_dp_in_wc, leakage_area_in2, required_cfm