Cooling Tower Approach and Range
Range, approach, heat rejection (gpm × 500 × range BTU/hr).
Example
You enter
- Entering water T (°F) 95
- Leaving water T (°F) 85
- Ambient wet-bulb (°F) 75
- Design flow (gpm) 300
- Fan kW (optional) 15
You get
- Range 10
- Approach 10
- Efficiency 0.5
- Heat rejection 1500000
- Approach flag in-range (5-10 °F)
- Range flag in-range (8-12 °F)
- Fan kW per ton 0.12
Details, formula, and sources
Range, approach, heat rejection (gpm × 500 × range BTU/hr), and fan kW per ton against typical 5-10 °F approach / 8-12 °F range targets.
Range = T_in − T_out. Approach = T_out − T_wb. Efficiency = range / (range + approach) = range / (T_in − T_wb). Heat rejection (BTU/hr) = gpm × 500 × range. Fan kW per ton = fan_kW × 12000 / heat_rejection.
Cooling Technology Institute (CTI) ATC-105 standard practice by name; ASHRAE Handbook (HVAC Systems and Equipment) cooling-tower chapter by name.
CTI guides free at cti.org outreach; ASHRAE Handbook licensed.
Estimate. AHJ and licensed mechanical contractor govern. ACCA Manual J / D / S supersede rules of thumb.
Field names used by the API: T_in_F, T_out_F, T_wb_F, gpm, fan_kW, range_F, approach_F, efficiency, heat_rejection_BTU_hr, approach_flag, range_flag, fan_kW_per_ton
- Constant 500 (8.34 lb/gal × 60 min/hr × cp = 1 BTU/lb-°F) ≈ 500 BTU/(hr · gpm · °F)physical-fact derivation for water
- Approach target band 5-10 °FCTI engineering practice
- Range target band 8-12 °FCTI engineering practice