Drying-System Balance (Installed Dehu vs Evaporation Load)

Checks whether the installed dehumidification keeps up with the estimated evaporation load.

Run the calculator

Example

You enter

You get

Checked against published worked examples from: ANSI/IICRC S500 balanced-drying-system principle.

Details, formula, and sources

ScopeThe balance in pints/day, the capacity-to-load ratio against a target margin, and a balanced / no-margin / deficit verdict with the capacity to add. Closes the loop between evaporation-load and dehumidifier. Field capacity falls below the AHAM nameplate as the air dries; the restorer's daily monitoring and IICRC S500 govern.

Formula or tablebalance_ppd = installed_ppd - evap_load_ppd; ratio = installed_ppd / evap_load_ppd; verdict from ratio against the target margin (default 1.2): >= margin balanced with margin, 1 to margin no margin, < 1 deficit (add margin x load - installed).

Source and editionBalanced-drying-system principle, by name; ANSI/IICRC S500. The capacity-to-load comparison is a field-arithmetic identity, not edition-bound.

Free accessCloses the loop between the evaporation-load and dehumidifier tiles: a balanced system keeps installed dehumidification at or above the evaporation load with margin.

What governsEstimate. AHJ and licensed professional govern.

API field namesevap_load_ppd, installed_ppd, target_margin, balance_ppd, ratio