Economic Conductor Sizing (I2R Payback)

Whether upsizing a conductor pays for itself in reduced I^2R heat loss.

Run the calculator

Example

You enter

You get

Details, formula, and sources

Three-phase loss = 3 x I^2 x R, so the annual saving = (loss at the small size - loss at the large) x run hours x rate, and payback = the added copper cost / that saving. A 100 A feeder from 0.20 to 0.125 ohm over 4,000 hr at $0.12 saves $1,080/yr, paying back an $800 upsize in 0.7 years; at 40 A the same upsize saves only $173/yr, a 4.6-year payback -- upsizing only pays on heavily loaded, long-hour feeders. A screening estimate; the code minimum still governs the conductor.

loss = 3 x I^2 x R / 1000 (kW, per size); annual_saving = (loss_small - loss_big) x hours x rate; payback = upsize_cost / annual_saving.

Economic (loss-based) conductor sizing, standard energy-engineering practice (NEC Informative Annex D / IEEE economic-conductor methods) by name; first-principles I^2R loss.

The three-phase I^2R loss and the payback arithmetic are first-principles; conductor resistances are in NEC Chapter 9 Table 8/9.

Estimate. AHJ and licensed professional govern.

Field names used by the API: current_a, r_small_ohm, r_big_ohm, hours, rate_kwh, upsize_cost, annual_saving, payback_yr