Voltage Drop
Single-phase or three-phase voltage drop over length.
Example
You enter
- Phase single
- Material copper
- AWG 10
- Length one-way (ft) 150
- Current (A) 20
- Source voltage (V) 240
You get
- Voltage drop 7.45 V
- Percent drop 3.11 %
Details, formula, and sources
VD = 2 * I * R * L for single-phase; VD = √3 * I * R * L for three-phase. R from NEC Chapter 9 Table 8 (DC ohm/kFT) with temperature correction; reactance per IEEE 141 for long runs.
NEC 2023 (NFPA 70). Chapter 9 Tables 8 and 9; IEEE 141 by name.
Free read-only access at nfpa.org/freeaccess. IEEE 141 is licensed; principles free at university OCW and IEEE-USA outreach.
Estimate. AHJ and licensed electrician govern. Verify against the NEC edition adopted in your jurisdiction.
Field names used by the API: phase, material, awg, length_ft, current_A, source_voltage_V, drop_V, percent
- Conductor temperature 75°C unless user suppliesNEC 310.15(B)(1)
- Power factor 0.85 for AC unless user suppliesengineering practice for general lighting / receptacle loads
- Voltage-drop target 3% branch + 5% feeder = 5% totalNEC informational notes 210.19(A)(1) FPN 4 / 215.2(A)(1) FPN 2