Wire Ampacity

Ampacity by gauge, conductor material, insulation rating, ambient.

Run the calculator

Example

You enter

You get

Checked against published worked examples from: NFPA.

Details, formula, and sources

Scopea heat-balance estimate that tracks NEC Table 310.16 through about 8 AWG and reads progressively HIGH above it (about 20% at 2 AWG, 40% at 4/0); size conductors from Table 310.16.

Formula or tableA steady-state thermal balance (I^2 R heating against convective and radiative surface loss) with the coefficient calibrated to a 75 C THWN #12 in 30 C ambient, times the NEC 310.15(C)(1) adjustment for more than 3 current-carrying conductors. NOT a Table 310.16 lookup; it reads high above about 8 AWG.

Source and editionNEC 2023 (NFPA 70).

Free accessFree read-only access at nfpa.org/freeaccess.

What governsEstimate. AHJ and licensed electrician govern. Verify against the NEC edition adopted in your jurisdiction.

API field namesawg, material, insulation_rating_C, ambient_C, bundle_count, ampacity_A