Breaker Sizing

Continuous-load 125 percent rule.

Run the calculator

Example

You enter

You get

Details, formula, and sources

OCP = 125% × continuous load + 100% × non-continuous load (NEC 210.19(A) / 215.2(A)(1) / 215.3); next-standard-size rule per NEC 240.4(B); standard sizes per NEC 240.6(A).

NEC 2023 (NFPA 70).

Free read-only access at nfpa.org/freeaccess.

Estimate. AHJ and licensed electrician govern. Verify against the NEC edition adopted in your jurisdiction.

Field names used by the API: load_A, continuous, required_A, next_standard_A