Service Load Calculation (Residential)

Standard demand factors over lighting, appliances, range, dryer, HVAC; output minimum service ampacity.

Run the calculator

Example

You enter

You get

Checked against published worked examples from: NFPA.

Details, formula, and sources

Formula or tableStandard method: general lighting and receptacle demand per NEC Table 220.45 (3 kVA at 100%, to 120 kVA at 35%, rest at 25%); range per Table 220.55 Column C; dryer per 220.54 (5 kW minimum when present); fixed appliances at 100% (the 75% of 220.53 needs an appliance count -- service-load-standard applies it); larger of heating or cooling per 220.60.

Source and editionNEC 2023 (NFPA 70). Article 220.

Free accessFree read-only access at nfpa.org/freeaccess.

What governsEstimate. AHJ and licensed electrician govern. Verify against the NEC edition adopted in your jurisdiction.

API field namesarea_ft2, small_appliance_circuits, laundry_circuits, fixed_appliances_W, range_W, dryer_W, hvac_cooling_W, hvac_heating_W, total_demand_W, required_A, next_standard_A