Service Entrance Demand Load (Standard Method)

NEC Article 220 Standard Method demand-factor walk; recommended service ampacity from the standard ladder.

Run the calculator

Example

You enter

You get

Checked against published worked examples from: NFPA.

Details, formula, and sources

Formula or tableStandard Method per NEC 2023 Table 220.45 (general lighting demand factors, 220.42 before 2023: first 3000 VA at 100%, next 117000 VA at 35%, remainder at 25%); 220.53 (fixed appliances 75% where four or more fastened-in-place appliances share the feeder or service); 220.54 (dryer 5000 W or nameplate, whichever is greater); 220.55 (range simplified); 430.24 (largest motor at 125%); 220.60 (HVAC larger of cooling vs. heating). Service A = total_VA / V; recommended service from the NEC 100/125/150/175/200/225/300/400 ladder.

Source and editionNEC 2023 (NFPA 70). Article 220 (Branch-Circuit, Feeder, and Service Load Calculations).

Free accessFree read-only access at nfpa.org/freeaccess.

What governsEstimate. AHJ and licensed electrician govern. Verify against the NEC edition adopted in your jurisdiction.

API field namesarea_ft2, small_appliance_circuits, laundry_circuit, fixed_appliances_W, fixed_appliance_count, range_W, dryer_W, largest_motor_W, hvac_cooling_W, hvac_heating_W, service_voltage, total_VA, required_A, recommended_A