Exterior Wall Opening Limit by Fire Separation Distance (IBC Table 705.10)

How much of an exterior wall may be windows and doors.

Run the calculator

Example

You enter

You get

Checked against published worked examples from: International Code Council.

Details, formula, and sources

ScopeCapped as a percentage of the wall area by the fire separation distance and by whether the openings are protected or the building sprinklered. A wall under 3 ft from the line gets none; at 5 to 10 ft a sprinklered wall may be 25% glass; at 30 ft or more there is no limit. The distance to the lot line, not the facade design, sets the glass - one of the strongest arguments for a sprinkler system on a wall tight to the property line. A design aid, not a code-official determination.

Formula or tableband = f(fsd_ft, protected) from Table 705.10 [705.8 in IBC 2021]; allowable_pct = band; allowable_area = band x wall_area (Infinity = no limit); pass = actual_opening <= allowable_area.

Source and editionIBC 2027 Table 705.10 [Table 705.8 in IBC 2021] (maximum area of exterior wall openings) and §705.3 (buildings on the same lot), by name.

Free accessThe opening-area limits are stated in the published IBC Table 705.10 (705.8 in 2021); the percentage comparison is public arithmetic.

What governsEstimate. AHJ and licensed professional govern.

API field namesfsd_ft, wall_area, protected, actual_opening, allowable_pct, allowable_area, pass