Fan Affinity Laws (Speed Change)

How far airflow, static pressure, and horsepower move when a fan's speed changes.

Run the calculator

Example

You enter

You get

Checked against published worked examples from: Twin City Fan.

Details, formula, and sources

ScopeFor a fixed fan changing speed: airflow scales with speed (Q2 = Q1 r), static with the square (SP2 = SP1 r^2), power with the cube (BHP2 = BHP1 r^3). 10,000 CFM / 1.0 in wg / 5.0 BHP from 900 to 1200 rpm -> 13,333 CFM, 1.78 in wg, 11.85 BHP; slowing to r 0.75 cuts power 58%, the VFD payback in one line. The fan curve governs.

Formula or tabler = N2/N1; Q2 = Q1 r; SP2 = SP1 r^2; BHP2 = BHP1 r^3.

Source and editionThe fan affinity (fan) laws for a speed change from AMCA / ASHRAE Handbook - Fundamentals, by name.

Free accessThe affinity laws (flow proportional to speed, pressure to speed squared, power to speed cubed) are standard published fan-engineering relations.

What governsEstimate. AHJ and licensed professional govern.

API field namesq1_cfm, sp1_inwg, bhp1_hp, n1, n2, r, q2_cfm, sp2_inwg, bhp2_hp