Generator Output Conductor at 115% (NEC 445.13)

The conductor rule from a generator to its first overcurrent device, which estimators routinely get wrong: NEC 445.13(A) sets the ampacity at not less than 115% of the generator NAMEPLATE current -- not 125% of a computed load, not the connected running load. A 150 kW, 480 V three-phase generator at 0.8 pf draws 225.6 A nameplate, so the conductor must carry 1.15 x 225.6 = 259.4 A. Where the design prevents output above nameplate (overload-limited), the basis drops to 100% and it is just 225.6 A. Enter the nameplate current directly or derive it from kW, voltage, phase, and pf. The 110.14(C) termination limit and 310.15 adjustments still apply. A design aid; the AHJ governs.

Run the calculator

Formula and source

nameplate = given, or kW x 1000 / (sqrt(3) x V x pf) three-phase, or kW x 1000 / (V x pf) single-phase; basis = overload_limited ? 1.00 : 1.15; required_ampacity = basis x nameplate.

The generator output-conductor ampacity rule of NEC 2023 445.13(A) -- not less than 115% of the generator nameplate current, or 100% where the design prevents output above the nameplate -- by name. A computational aid; the AHJ-adopted NEC edition governs.

Audience

This tile is built for electricians and the adjacent professions in the Electrical group. The interactive calculator runs entirely in your browser. No account, no fee, no advertising, no tracking.

Related tools

Posture

Rough Logic answers the math question the working professional asks on the job. The site is a calm, fast, ad-free, account-free, ever-free reference. It does not interpret code. It does not replace the licensed professional. It does not store your inputs. The Authority Having Jurisdiction governs all installations and inspections.