Also in: Disaster Response and Recovery

Generator Sizing for Motor Starting

Required generator kW / kVA from running load and motor-starting kVA at the 30% voltage-dip criterion.

Run the calculator

Example

You enter

You get

Checked against published worked examples from: NEC 430.110 + manufacturer locked-rotor schedule (project bundled); Cummins Power Generation.

Details, formula, and sources

Formula or tableSteady kW = Σ running_kW + non_motor_kW. Worst starting kVA = max over motors of starting_kVA(motor); starting_kVA = HP × code_kVA_per_HP from the NEMA MG-1 code letter, OR LRA × V × √phases / 1000 if the user supplies LRA. Required gen kVA = worst_starting_kVA x X'd x (1 - dip) / dip x starts factor (1.0 / 1.15 / 1.30), the reactance divider dip = X'd S_m / (S_gen + X'd S_m) solved for S_gen, with X'd the generator transient reactance (default 0.25 per unit) and dip_factor (0.30 default per the 30% voltage-dip criterion). Required kW = max(steady, required_starting_kVA × 0.8).

Source and editionNEMA MG-1 (Motors and Generators) by name; engineering-practice 30% voltage-dip criterion for transient motor starts.

Free accessNEMA MG-1 licensed; code-letter principles free in published power-engineering texts.

What governsEstimate. AHJ and licensed electrician govern. Verify against the NEC edition adopted in your jurisdiction.

API field namesmotors, non_motor_kW, dip_factor, starts_per_hour, running_kW, worst_starting_kVA, required_starting_kVA, required_kW, recommended_kW

Related tools