Grounding Electrode Conductor Sizing

The grounding electrode conductor (GEC) from the largest ungrounded service conductor per NEC Table 250.66.

Run the calculator

Example

You enter

You get

Checked against published worked examples from: IAEI Magazine (Keith Lofland).

Details, formula, and sources

ScopeWith the 250.66(A)-(C) electrode caps applied: a rod/pipe/plate sole connection need not exceed 6 AWG copper, a concrete-encased (Ufer) 4 AWG copper, while a water-pipe or structural-steel electrode takes the full table size. The AHJ-adopted edition governs.

Formula or tableGEC from NEC Table 250.66 by the largest ungrounded service conductor (or equivalent parallel area), then the 250.66(A)-(C) electrode caps: rod/pipe/plate sole connection not larger than 6 AWG copper / 4 AWG aluminum; concrete-encased not larger than 4 AWG copper; ground ring sole connection not required to be larger than the ring conductor (at least 2 AWG copper, 250.52(A)(4)), so capped at 2 AWG copper for the minimum ring; water-pipe / structural-steel electrode takes the full table size.

Source and editionNEC 2023 (NFPA 70). Section 250.66 and Table 250.66.

Free accessFree read-only access at nfpa.org/freeaccess.

What governsEstimate. AHJ and licensed electrician govern. Verify against the NEC edition adopted in your jurisdiction.

API field namesservice_kcmil, material, electrode_type, required_gec, base_gec