Humidifier Capacity (RH Target)

Moisture addition (lb/hr, gal/day) and latent load from supply CFM and the entering-to-target RH rise.

Run the calculator

Example

You enter

You get

Details, formula, and sources

With altitude-corrected humidity ratios. Per ASHRAE Fundamentals 2021 Ch. 1 psychrometrics.

Moisture addition (lb/hr) = 60 × CFM × rho × (W_target − W_entering); W = 0.621945 × Pw / (P − Pw) with Pw = RH × Pws(T_db) and P the altitude-corrected pressure. Daily water = lb/hr × 24 / 8.34. Latent load = addition × 1061 BTU/lb.

ASHRAE Fundamentals 2021 Chapter 1 (psychrometrics) by name.

ASHRAE Handbook TOC free at ashrae.org; full handbook licensed.

Estimate. AHJ and licensed mechanical contractor govern. ACCA Manual J / D / S supersede rules of thumb.

Field names used by the API: cfm, supply_db_F, entering_rh_pct, target_rh_pct, addition_lb_hr, gpd, latent_btu_hr