Hydrant Flow
GPM from Pitot pressure and outlet diameter.
Example
You enter
- Pitot pressure (psi) 10
- Outlet diameter (in) 2.5
- Coefficient of discharge 0.9
You get
- Flow 530 gpm
Checked against published worked examples from: NFPA.
Details, formula, and sources
Formula or tableFlow GPM = 29.83 × c × d² × sqrt(P_pitot). c = coefficient of discharge (0.90 typical for rounded outlets, 0.80 for square outlets, 0.70 for cocked-back outlets).
Source and editionAWWA M17 (Installation, Field Testing, and Maintenance of Fire Hydrants) by name; ISO Public Protection Classification fire-flow methodology.
Free accessAWWA M17 licensed; principles free at most state-DOT and water-utility training pages.
What governsEstimate. AHJ and licensed fire protection engineer govern.
API field namespitot_psi, outlet_diameter_in, c, flow_gpm
- Default coefficient 0.90 (rounded outlet) unless user suppliesAWWA M17 typical