Insulation Resistance PI / DAR (Megger Test)

The polarization index (PI) and dielectric absorption ratio (DAR) from a timed insulation-resistance (megger) test -- the ratios that tell whether a motor, generator, or transformer winding is clean and dry or wet and contaminated. Good insulation keeps absorbing charge, so its resistance keeps RISING over the test; wet or dirty insulation stops rising or falls. DAR = IR(60 s)/IR(30 s); PI = IR(10 min)/IR(1 min) (the 1-minute and 60-second readings are the same). By IEEE 43, PI below 1 is dangerous, 1-2 questionable, 2-4 good, above 4 excellent; DAR below 1.25 is marginal, 1.4+ good. An 800/1,040/4,160 Mohm test gives DAR 1.30, PI 4.0. A trend/screen, not a pass/fail: temperature-correct to a common base first, and on very-high-IR epoxy windings PI loses meaning per IEEE 43. The baseline trend and OEM criteria govern.

Run the calculator

Formula and source

dar = IR(60 s) / IR(30 s); polarization_index = IR(10 min) / IR(1 min). IEEE 43 bands: PI < 1 dangerous, 1-2 questionable, 2-4 good, > 4 excellent; DAR < 1.25 marginal, 1.4+ good.

IEEE 43 (Recommended Practice for Testing Insulation Resistance of Electric Machinery) polarization index and dielectric absorption ratio, by name; the machine baseline trend and the OEM acceptance criteria govern.

Audience

This tile is built for electricians and the adjacent professions in the Electrical group. The interactive calculator runs entirely in your browser. No account, no fee, no advertising, no tracking.

Related tools

Posture

Rough Logic answers the math question the working professional asks on the job. The site is a calm, fast, ad-free, account-free, ever-free reference. It does not interpret code. It does not replace the licensed professional. It does not store your inputs. The Authority Having Jurisdiction governs all installations and inspections.