Loop-Powered (2-Wire) 4-20 mA Transmitter Voltage Budget

Whether a loop-powered 2-wire 4-20 mA transmitter has enough voltage to operate. The transmitter needs a minimum terminal (compliance / lift-off) voltage -- commonly 8-12 Vdc -- and at the 20 mA top of range the loop supply must push that current through ALL the series resistance (the sense/load resistor, the round-trip wire, plus barriers) and still leave the transmitter its minimum. Max total loop resistance = (supply - transmitter minimum) / 0.020; voltage at the transmitter = supply - 0.020 x total series resistance. A 24 Vdc loop with a 250 ohm sense resistor and 50 ohm of wire (300 ohm) leaves 18 V -- fine above a 10.5 V minimum -- and could carry up to 675 ohm; a 600 ohm run (850 ohm total) starves it at 7 V and the loop reads wrong. DC worst case at 20 mA; the transmitter datasheet's compliance voltage and the barrier burden govern.

Run the calculator

Formula and source

max_loop_resistance = (supply_v - transmitter_min_v) / 0.020; voltage_at_transmitter = supply_v - 0.020 x (load_resistance + wire_resistance); within_spec when voltage_at_transmitter >= transmitter_min_v.

Loop-powered (2-wire) 4-20 mA transmitter voltage-budget / maximum-load-resistance relation by name (transmitter compliance-voltage practice; Ohm's law at the 20 mA worst case); the transmitter datasheet governs.

Audience

This tile is built for trades and the adjacent professions in the Electrical group. The interactive calculator runs entirely in your browser. No account, no fee, no advertising, no tracking.

Related tools

Posture

Rough Logic answers the math question the working professional asks on the job. The site is a calm, fast, ad-free, account-free, ever-free reference. It does not interpret code. It does not replace the licensed professional. It does not store your inputs. The Authority Having Jurisdiction governs all installations and inspections.