Moist Air Enthalpy (ASHRAE Psychrometrics)

Total heat content h = 0.240 t + W (1061 + 0.444 t) Btu per lb dry air.

Run the calculator

Example

You enter

You get

Checked against published worked examples from: ASHRAE.

Details, formula, and sources

ScopeThe state property every coil and air-mix calculation starts from. Return air at 80 F, W 0.0112 -> 31.48 Btu/lb; 55 F supply, W 0.009 -> 22.97. Pair with an outdoor-air mix calculation for W. A design aid; the chart and equipment ratings govern.

Formula or tableh = 0.240 t + W (1061 + 0.444 t) Btu per lb dry air.

Source and editionThe I-P moist-air enthalpy relation from the ASHRAE Handbook - Fundamentals, by name.

Free accessThe moist-air enthalpy relation and its sea-level coefficients are standard ASHRAE psychrometric results. A measured chart state and the equipment ratings govern.

What governsEstimate. AHJ and licensed professional govern.

API field namest_db_f, w_lb_lb, h