Measured Outside-Air Percent from Mixed-Air Temperatures

How much outside air a unit is actually pulling in, read from three temperatures.

Run the calculator

Example

You enter

You get

Details, formula, and sources

%OA = 100 (T_ra - T_ma) / (T_ra - T_oa), the field check of the outside-air damper against the design minimum. RA 75, MA 68, OA 40 F -> 20% OA; the damper opening to MA 63 reads 34%. A mixed-air temp outside the return/outdoor band flags a sensor fault; a spread under 10 F warns of low reliability. A field aid.

%OA = 100 (T_ra - T_ma) / (T_ra - T_oa).

The mixed-air temperature balance for the outside-air fraction from ASHRAE / AABC-NEBB field practice, by name.

The mixed-air temperature-balance outside-air percentage is a standard published air-balancing field check.

Estimate. AHJ and licensed professional govern.

Field names used by the API: t_ra_f, t_ma_f, t_oa_f, pct_oa