Power Distro Per-Leg Loading

Current per leg, percent of service rating, headroom.

Run the calculator

Example

You enter

You get

Details, formula, and sources

Current per leg, percent of service rating, headroom, and a pass/fail against the 80% continuous limit for stage/event temporary power, 1-phase or 3-phase.

1-phase I = W/(V*PF); 3-phase I = W/(sqrt(3)*V_LL*PF); %load = I/rating*100; continuous limit = rating*0.80.

First-principles AC power (P = V*I*PF; 3-phase adds sqrt(3)); the NEC continuous-load 80% rule and temporary-power Articles 520/525, by name.

NFPA 70 free read-only at nfpa.org/freeaccess; a qualified electrician and the AHJ govern temporary power.

Estimate. AHJ and licensed electrician govern. Verify against the NEC edition adopted in your jurisdiction.

Field names used by the API: watts, voltage_v, phase, rating_a, pf, derate, amps_per_leg, pct_load