Also in: Disaster Response and Recovery

Power Distro Per-Leg Loading

Current per leg, percent of service rating, headroom.

Run the calculator

Example

You enter

You get

No published worked example is on file for this calculation. It is checked against a hand-worked derivation of its method and an independent reference test.

Details, formula, and sources

ScopeCurrent per leg, percent of service rating, headroom, and a pass/fail against the 80% continuous limit for stage/event temporary power, 1-phase or 3-phase.

Formula or table1-phase I = W/(V*PF); 3-phase I = W/(sqrt(3)*V_LL*PF); %load = I/rating*100; continuous limit = rating x the entered continuous-derate target (0.80 for the NEC 80% rule).

Source and editionFirst-principles AC power (P = V*I*PF; 3-phase adds sqrt(3)); the NEC continuous-load 80% rule and temporary-power Articles 520/525, by name.

Free accessNFPA 70 free read-only at nfpa.org/freeaccess; a qualified electrician and the AHJ govern temporary power.

What governsEstimate. AHJ and licensed electrician govern. Verify against the NEC edition adopted in your jurisdiction.

API field nameswatts, voltage_v, phase, rating_a, pf, derate, amps_per_leg, pct_load