Dead-load screen for a ballasted flat-roof PV array: total = modules x (module weight + ballast) + racking; added pressure = total / array area, compared to the allowable. 30 modules at 50 lb plus 40 lb of ballast each on a 150 lb rack is 2,850 lb over 630 sf -- 4.5 psf, under a 5 psf allowable; push the ballast to 60 lb and it is 5.48 psf, over the line. A SCREEN, not a design -- the PE-stamped ballast plan and the structural engineer govern; wind uplift and the roof structure govern the design.

Run the calculator

Formula and source

total_wt_lb = modules x (module_wt_lb + ballast_per_module_lb) + racking_wt_lb; added_psf = total_wt_lb / array_area_sf; pass = added_psf <= allowable_psf.

PV ballast load-screen identity by name (total dead load over the array footprint, screened against the allowable); first-principles arithmetic.

Audience

This tile is built for trades and the adjacent professions in the Electrical group. The interactive calculator runs entirely in your browser. No account, no fee, no advertising, no tracking.

Related tools

Posture

Rough Logic answers the math question the working professional asks on the job. The site is a calm, fast, ad-free, account-free, ever-free reference. It does not interpret code. It does not replace the licensed professional. It does not store your inputs. The Authority Having Jurisdiction governs all installations and inspections.