PV Circuit Maximum Current and Ampacity (NEC 690.8, the 156% Rule)

PV circuit maximum current and the minimum conductor ampacity it requires.

Run the calculator

Example

You enter

You get

Details, formula, and sources

Sizes the PV source/output-circuit maximum current = module Isc x paralleled strings x 125% (690.8(A)(1)) and the minimum conductor ampacity = that maximum x another 125% (690.8(B)(1)), the two factors stacking to 156% of Isc, before any conditions-of-use derate. The conductor must also satisfy 690.8(B)(2) and the greater governs; the engineer governs.

max_current = Isc x strings x 1.25 (690.8(A)(1)); min_ampacity = max_current x 1.25 (690.8(B)(1)); the factors stack to 1.5625 (156%) of Isc, before conditions-of-use derate; also size for 690.8(B)(2) and take the greater.

PV source/output-circuit current and conductor ampacity, NEC 2023 690.8(A) and 690.8(B), by name.

NEC is free to read at nfpa.org/freeaccess. The two 125% factors stack to 156% of Isc; the conductor must also satisfy 690.8(B)(2) after temperature/conduit conditions of use, and the greater of (B)(1) and (B)(2) governs.

Estimate. AHJ and licensed electrician govern. Verify against the NEC edition adopted in your jurisdiction.

Field names used by the API: module_isc_a, parallel_strings, max_current_a, min_ampacity_a, stacked_factor