PVC Raceway Expansion Fitting

PVC conduit thermal length change, whether an expansion fitting is required (>= 0.25 in).

Run the calculator

Example

You enter

You get

Checked against published worked examples from: NEC Article 352.44 / Table 352.44 (by name).

Details, formula, and sources

ScopePVC conduit thermal length change, whether an expansion fitting is required (>= 0.25 in), and the fitting count from the run length and temperature range (NEC 352.44).

Formula or tabledL = alpha * L * dT with alpha = 3.38e-5 in/in/F (NEC Table 352.44 PVC); an expansion fitting is required where dL >= 0.25 in in a straight run; fittings = ceil(dL / fitting_travel).

Source and editionPVC raceway thermal expansion and expansion-fitting sizing - the length change over the run from the temperature range, the 0.25 in straight-run threshold, and the fitting count - per NEC Article 352.44 and Table 352.44 (rigid PVC conduit), by name; first-principles linear expansion.

Free accessNEC is free to read at nfpa.org/freeaccess. The 3.38e-5 in/in/F PVC-conduit coefficient is the NEC Table 352.44 figure, distinct from PVC pipe.

What governsEstimate. AHJ and licensed electrician govern. Verify against the NEC edition adopted in your jurisdiction.

API field namesrun_length_ft, temp_range_f, alpha_per_f, fitting_travel_in, length_change_in, fittings_needed