SCBA Cylinder Work Time

Time to low-air alarm and to empty from rated scf, current pressure, alarm pressure, and consumption rate.

Run the calculator

Example

You enter

You get

Checked against published worked examples from: NFPA / NIOSH.

Details, formula, and sources

ScopeNFPA 1981 governs cylinder ratings; exit at the alarm, not at empty.

Formula or tableavailable_scf_to_alarm = (P_start - P_alarm) / P_rated * V_rated. time_to_alarm_min = available_scf / consumption_scfm. Time-to-empty is a math aid only; exit at the low-air alarm.

Source and editionNFPA 1981-2019; NIOSH 42 CFR 84.

Free accessnfpa.org/freeaccess for NFPA 1981 TOC; ecfr.gov for 42 CFR 84.

What governsEstimate. AHJ and licensed fire protection engineer govern.

API field namesV_rated_scf, P_rated_psi, P_start_psi, P_alarm_psi, consumption_lpm, available_scf_to_alarm, time_to_alarm_min, time_to_empty_min