Shock Approach Boundaries (NFPA 70E Table 130.4)

Looks up the NFPA 70E Table 130.4 AC shock approach boundaries by nominal voltage.

Run the calculator

Example

You enter

You get

Checked against published worked examples from: NFPA 70E-2024.

Details, formula, and sources

ScopeThe limited approach (separate distances for an exposed movable conductor vs a fixed circuit part) and the restricted approach. Below 50 V no boundary is specified. Shock boundaries only (the arc-flash boundary is separate); the employer's safety program and 70E govern.

Formula or tablelookup by nominal phase-to-phase AC voltage band: limited approach (exposed movable conductor vs exposed fixed circuit part) and restricted approach; below 50 V no boundary is specified.

Source and editionAC shock approach boundaries, NFPA 70E-2024 Table 130.4, by name.

Free accessNFPA 70E is free to read at nfpa.org/freeaccess. These are shock boundaries only; the arc-flash boundary is a separate determination. Crossing the restricted approach requires a qualified person, an energized-work permit, and shock PPE.

What governsEstimate. AHJ and licensed electrician govern. Verify against the NEC edition adopted in your jurisdiction.

API field namesnominal_v_ac, limited_fixed, restricted, no_boundary