Shotcrete / Gunite Order Quantity with Rebound

Cubic yards of shotcrete or gunite to order once rebound (the fraction that bounces off and never stays) is grossed up.

Run the calculator

Example

You enter

You get

Details, formula, and sources

shot = in-place / (1 - rebound). A 500 sf face at 4 in holds 6.17 cy but needs 7.72 cy shot at 20% rebound, 8.82 cy at 30%. The applicator's field rebound governs.

in_place_cy = area_sf x (thickness_in/12) / 27; shot_cy = in_place_cy / (1 - rebound_pct/100); rebound_cy = shot_cy - in_place_cy.

Rebound gross-up identity by name (ACI 506 shotcrete practice); first-principles volume arithmetic.

The rebound gross-up identity is public shotcrete practice; ACI 506R describes rebound ranges.

Estimate. AHJ and licensed professional govern.

Field names used by the API: area_sf, thickness_in, rebound_pct, shot_actual_cy, in_place_cy, shot_cy, rebound_cy, naive_add_cy, in_place_from_shot_cy, achieved_thickness_in