Sliding Snow Load on a Lower Roof (ASCE 7 7.9)

The surcharge from snow sliding off a slippery upper roof onto a lower roof.

Run the calculator

Example

You enter

You get

Checked against published worked examples from: AWC / M. O'Rourke, R. Mazikins, J. Showalter.

Details, formula, and sources

Scopetotal = 0.4 x the upper roof's flat snow load Pf x its eave-to-ridge length W (lb/ft), distributed over the lesser of 15 ft or the lower-roof width. A 20 psf / 40 ft upper roof drops 320 lb/ft, which over 15 ft is a 21.3 psf surcharge; a narrow 10 ft catch roof takes only its 10/15 share, 213 lb/ft at the same 21.3 psf (the rest falls off). Adds to the lower roof's own balanced load. A design aid, not a substitute for the engineer of record.

Formula or tabletotal = 0.4 x pf_upper x W (lb/ft) over 15 ft, reduced in proportion (x lower_width / 15) on a lower roof narrower than 15 ft; surcharge = total / distribution width (psf).

Source and editionThe ASCE 7 §7.9 sliding snow load on a lower roof, by name.

Free accessASCE 7 is available through the ASCE Library at ascelibrary.org; the §7.9 sliding-load relation is public.

What governsEstimate. AHJ and licensed professional govern.

API field namespf_upper_psf, eave_ridge_ft, lower_width_ft, total_lb_ft, surcharge_psf