Smoke Alarm Count and Placement (IRC R310)

Two halves people confuse. The COUNT is additive and gets undercounted.

Run the calculator

Example

You enter

You get

Checked against published worked examples from: International Code Council.

Details, formula, and sources

ScopeOne in each sleeping room, one OUTSIDE each separate sleeping area, and one on each additional story including basements and habitable attics -- three bedrooms, one sleeping area, one extra story is five, minimum. The CLEARANCE from a permanently installed cooking appliance depends on the code edition: the 2024 IRC sets 10 ft for every alarm, 6 ft only where 10 ft would block a required location; the 2021 IRC set it by sensing type -- 20 ft ionization, 10 ft ionization with a silencing switch, 6 ft photoelectric or nuisance-listed -- so there a type change could fix a failing spot. Also the 3 ft separation from a tub/shower bathroom door.

Formula or tableminimum alarms = sleeping rooms + separate sleeping areas + additional stories; required cooking clearance = 10 ft for any sensing type, or 6 ft where 10 ft would prevent a required location (IRC 2024, the default); under IRC 2021, 20 ft (ionization), 10 ft (ionization with a silencing switch), or 6 ft (photoelectric, or marked to reduce cooking nuisance alarms); bathroom separation = 3 ft horizontally from the door or opening of a bathroom with a tub or shower.

Source and editionIRC 2024 R310.3 [R314.3 in IRC 2021] Location and R310.3.1 [R314.3.1 in IRC 2021] Installation near cooking appliances; the IRC 2021 cooking distances are selectable.

Free accessBoth provisions are short prescriptive sentences reproduced in state adoptions and building-department bulletins. No table is reproduced.

What governsEstimate. AHJ and licensed professional govern.

API field namessleeping_rooms, sleeping_areas, additional_stories, alarm_type, distance_to_cooking_ft, distance_to_bath_door_ft, code_edition, required_alarms, required_cooking_ft, cooking_deficit_ft, bath_deficit_ft