Sprinkler GPM Density

Total gpm from area of operation and density (gpm/ft^2).

Run the calculator

Example

You enter

You get

Checked against published worked examples from: NFPA.

Details, formula, and sources

Formula or tableSprinkler demand GPM = density (gpm/ft²) × area_of_operation (ft²) per the NFPA 13 density/area design approach (Chapter 19 since the 2019 edition; §11.2 in 2013/2016); the hose-stream allowance is added separately and is not in this total.

Source and editionNFPA 13 (2022) Chapter 19 (design approaches: density/area curves and hose-stream allowance) by name.

Free accessNFPA 13 read-only at nfpa.org/freeaccess.

What governsEstimate. AHJ and licensed fire protection engineer govern.

API field namesarea_of_operation_ft2, hazard_category, total_gpm, density_gpm_per_ft2, meets_minimum, hazard_minimum_density