Raceway / Cable Support-Spacing Lookup (NEC Chapter 3)

The securing and support intervals for the common wiring methods from their NEC Chapter 3 .30 sections: EMT within 3 ft of a box and every 10 ft, NM within 12 in and every 4.5 ft, MC within 12 in and every 6 ft, AC within 12 in and every 4.5 ft; RMC and PVC intervals vary with trade size. The securing exceptions (fishing, terminations) and the AHJ govern.

Run the calculator

Formula and source

by wiring method: EMT secure within 36 in, support every 10 ft (358.30); NM within 12 in, every 4.5 ft (334.30); MC within 12 in, every 6 ft (330.30); AC within 12 in, every 4.5 ft (320.30); RMC/PVC intervals vary with trade size.

Securing and supporting sections of NEC 2023 Chapter 3 (320.30, 330.30, 334.30, 344.30, 352.30, 358.30), by name.

Audience

This tile is built for electricians and the adjacent professions in the Electrical group. The interactive calculator runs entirely in your browser. No account, no fee, no advertising, no tracking.

Related tools

Posture

Rough Logic answers the math question the working professional asks on the job. The site is a calm, fast, ad-free, account-free, ever-free reference. It does not interpret code. It does not replace the licensed professional. It does not store your inputs. The Authority Having Jurisdiction governs all installations and inspections.