Raceway / Cable Support-Spacing Lookup (NEC Chapter 3)

The securing and support intervals for the common wiring methods from their NEC Chapter 3 .30 sections.

Run the calculator

Example

You enter

You get

Details, formula, and sources

EMT within 3 ft of a box and every 10 ft, NM within 12 in and every 4.5 ft, MC within 12 in and every 6 ft, AC within 12 in and every 4.5 ft; RMC and PVC intervals vary with trade size. The securing exceptions (fishing, terminations) and the AHJ govern.

by wiring method: EMT secure within 36 in, support every 10 ft (358.30); NM within 12 in, every 4.5 ft (334.30); MC within 12 in, every 6 ft (330.30); AC within 12 in, every 4.5 ft (320.30); RMC/PVC intervals vary with trade size.

Securing and supporting sections of NEC 2023 Chapter 3 (320.30, 330.30, 334.30, 344.30, 352.30, 358.30), by name.

NEC is free to read at nfpa.org/freeaccess. RMC and PVC maximum intervals vary with trade size (the size-specific tables govern); some methods have securing exceptions (fishing, terminations).

Estimate. AHJ and licensed electrician govern. Verify against the NEC edition adopted in your jurisdiction.

Field names used by the API: wiring_method, secure_within_in, max_interval_ft