Resistance / Spot-Welder Branch-Circuit Conductor and OCPD (NEC 630.31)
Sizes a resistance (spot / seam / projection) welder branch circuit.
Example
You enter
- Nameplate primary current (A) 100
- Duty cycle (%) 50
You get
- Conductor current (size to) 71
- Max overcurrent device 300
Checked against published worked examples from: NFPA (National Electrical Code Handbook).
Details, formula, and sources
ScopeBecause the welder fires in brief pulses, the conductor carries the primary current times the Table 630.31(A)(2) duty multiplier (the printed value at a listed duty, 0.71 at 50%; the square root of the duty between rows; 0.22 at 5% or less), the same duty-derating idea as an arc welder. A 100 A primary, 50%-duty spot welder needs conductors rated 71 A (a #4 Cu at 75 C). But the overcurrent device may run up to 300% of the rated primary (NEC 630.32(A)) -- higher than the 200% for arc welders -- so the pulses do not nuisance-trip it: up to a 300 A device on that welder. Use the nameplate rated primary current and duty cycle; the AHJ, the welder nameplate, and the adopted NEC edition govern. Arc welders use the separate 630.11/630.12 (200%) method.
Formula or tableduty_multiplier = the Table 630.31(A)(2) value at a listed duty cycle (50% 0.71, 40% 0.63, 30% 0.55, 25% 0.50, 20% 0.45, 15% 0.39, 10% 0.32, 7.5% 0.27, 5% or less 0.22), else sqrt(duty_pct / 100), the relation the table rounds; conductor_current_a = primary_current_a x duty_multiplier; ocpd_max_a = 3.0 x primary_current_a (630.32(A)).
Source and editionNEC 630.31 (conductors) and 630.32 (overcurrent protection) for resistance welding equipment, by name; the welder nameplate and the adopted NEC edition govern.
Free accessThe duty-cycle conductor derating and the 300% OCPD limit are public NEC (many jurisdictions post the adopted NEC); the rated primary current and duty come from the welder nameplate.
What governsEstimate. AHJ and licensed professional govern.
API field namesprimary_current_a, duty_pct, conductor_current_a, ocpd_max_a
- Duty multiplier conductor at I_primary x the Table 630.31(A)(2) value at a listed duty, sqrt(duty) between rows, 0.22 at 5% or less, for a specific nonrepetitive welderNEC 630.31
- OCPD 300% resistance-welder overcurrent device up to 300% of the rated primary (630.32(A)); arc welders are 200%NEC 630.32