Chemical Metering-Pump Setting

Neat chemical (lb/day), solution feed (GPD and mL/min), and pump setting (% of max) from plant flow, target dose.

Run the calculator

Example

You enter

You get

Details, formula, and sources

Solution strength, and specific gravity via the pounds formula.

pure lb/day = MGD*dose*8.34; solution lb/day = pure/(strength/100); GPD = solution_lb_day/(8.34*SG); mL/min = GPD*3785.41/1440; setting% = GPD/pump_max*100.

Pounds-formula basis (lb/day = MGD x mg/L x 8.34), standard AWWA / EPA water-operator practice, by name.

Public pounds formula; the operator of record and primacy agency govern.

Estimate. AHJ and licensed professional govern.

Field names used by the API: flow_mgd, dose_mgl, strength_pct, sg, pump_max_gpd, setting_pct, solution_gpd