Hot-Aisle Containment Bypass Airflow

Balances IT airflow against cooling-unit supply, calculates bypass fraction and mixed return temperature.

Run the calculator

Example

You enter

You get

Details, formula, and sources

Balances IT airflow against cooling-unit supply, calculates bypass fraction and mixed return temperature, and tests one- and two-unit failure cases. It also estimates fan-energy savings from eliminating bypass; commissioning measurements govern.

IT airflow = IT kW x 3,412/(1.08 x equipment delta-T); bypass = supply - IT airflow; mixed return follows the sensible heat balance; fan power varies with airflow cubed.

First-principles airflow mixing and the fan affinity laws, with ASHRAE TC 9.9 thermal guidance. Rack-level inlet surveys and commissioning measurements govern.

Mass/heat balance plus the public cube-law fan relation.

Estimate. AHJ and licensed professional govern.

Field names used by the API: it_load_kw, equipment_delta_t_f, unit_count, airflow_per_unit_cfm, supply_temp_f, exhaust_temp_f, fan_power_per_unit_kw, tariff_per_kwh, it_airflow_cfm, bypass_fraction_pct, return_temp_f, annual_fan_savings, two_failed_margin_cfm