Duct Friction Loss and Static Pressure

Darcy-Weisbach with Swamee-Jain Colebrook; round or rectangular; fitting losses from a C_o library.

Run the calculator

Example

You enter

You get

Checked against published worked examples from: ASHRAE Fundamentals Darcy-Weisbach + ACCA Manual D fitting tables.

Details, formula, and sources

ScopeTotal external static.

Formula or tableHydraulic diameter D_h = 4A/P (round D_h = D), used with the duct's own velocity in the friction-factor and loss terms; the rectangular Huebscher equivalent round D_eq = 1.30 × (W×H)^0.625 / (W+H)^0.250 is reported for sizing and is not mixed into the loss. Velocity V_fpm = CFM / A. Velocity pressure VP = (V/4005)². Friction factor from Swamee-Jain explicit Colebrook: f = 0.25 / [log10(eps/(3.7 D) + 5.74/Re^0.9)]². Pressure loss dP = f × (L/D) × (rho_air × V²/(2g)) converted to in WC. Fitting losses dP_fit = Σ (C_o × VP).

Source and editionASHRAE Handbook, Fundamentals volume, Duct Design chapter (ch. 21), by name; principles in published engineering texts.

Free accessFree read-only access to ASHRAE standards at ashrae.org (Technical Resources, read-only standards).

What governsEstimate. AHJ and licensed mechanical contractor govern. ACCA Manual J / D / S supersede rules of thumb.

API field namesshape, D_in, material, cfm, length_ft, fittings, velocity_fpm, friction_loss_per_100ft_in_wc, straight_loss_in_wc, hydraulic_diameter_in