Manual D Friction Rate (Available Static Pressure)

The static pressure left over for the duct after the equipment takes its share, and the friction rate that sizes it.

Run the calculator

Example

You enter

You get

Details, formula, and sources

ASP = blower ESP - component drops, friction rate FR = ASP x 100 / total effective length (in wg/100 ft). 0.60 ESP, 0.42 drops, 180 ft TEL -> 0.18 ASP, 0.10 FR (a healthy target); a 300 ft run softens it to 0.06, needing larger ducts. Drops above the blower static flag an unworkable system. The full Manual D layout governs.

ASP = blower_ESP - component_drops; FR = ASP x 100 / TEL (in wg per 100 ft).

The ACCA Manual D friction rate (available static pressure over total effective length), by name.

The available-static-pressure and friction-rate relations are the published ACCA Manual D residential duct-design method.

Estimate. AHJ and licensed professional govern.

Field names used by the API: blower_esp_inwg, component_drop_inwg, tel_ft, asp_inwg, fr_inwg_100ft