Manual D Friction Rate (Available Static Pressure)

ASP = blower ESP - component drops, friction rate FR = ASP x 100 / total effective length (in wg/100 ft). 0.60 ESP, 0.42 drops, 180 ft TEL -> 0.18 ASP, 0.10 FR (a healthy target); a 300 ft run softens it to 0.06, needing larger ducts. Drops above the blower static flag an unworkable system. The full Manual D layout governs.

Run the calculator

Formula and source

ASP = blower_ESP - component_drops; FR = ASP x 100 / TEL (in wg per 100 ft).

The ACCA Manual D friction rate (available static pressure over total effective length), by name.

Audience

This tile is built for hvac and the adjacent professions in the HVAC group. The interactive calculator runs entirely in your browser. No account, no fee, no advertising, no tracking.

Related tools

Posture

Rough Logic answers the math question the working professional asks on the job. The site is a calm, fast, ad-free, account-free, ever-free reference. It does not interpret code. It does not replace the licensed professional. It does not store your inputs. The Authority Having Jurisdiction governs all installations and inspections.