Manual D Friction Rate (Available Static Pressure)

The static pressure left over for the duct after the equipment takes its share, and the friction rate that sizes it.

Run the calculator

Example

You enter

You get

Checked against published worked examples from: ACCA / Energy Efficiency Partnership; Shums Coda Associates.

Details, formula, and sources

ScopeASP = blower ESP - component drops, friction rate FR = ASP x 100 / total effective length (in wg/100 ft). 0.60 ESP, 0.42 drops, 180 ft TEL -> 0.18 ASP, 0.10 FR (a healthy target); a 300 ft run softens it to 0.06, needing larger ducts. Drops above the blower static flag an unworkable system. The full Manual D layout governs.

Formula or tableASP = blower_ESP - component_drops; FR = ASP x 100 / TEL (in wg per 100 ft).

Source and editionThe ACCA Manual D friction rate (available static pressure over total effective length), by name.

Free accessThe available-static-pressure and friction-rate relations are the published ACCA Manual D residential duct-design method.

What governsEstimate. AHJ and licensed professional govern.

API field namesblower_esp_inwg, component_drop_inwg, tel_ft, asp_inwg, fr_inwg_100ft