Evaporator Design TD and Humidity Band

The design split between box temperature and suction, and the humidity it holds in the box.

Run the calculator

Example

You enter

You get

Checked against published worked examples from: Heatcraft Refrigeration Products.

Details, formula, and sources

ScopeDTD = box temp - saturated suction, which sets the box humidity: 7-9 F ~90% RH (produce), 10-12 F ~80-85% (packaged meats), 12-16 F ~65-80%, 17-22 F ~50-65%. A 35 F box on a 25 F SST -> 10 F TD, ~80-85% RH (Heatcraft's beef-cooler example); a drying 17 F suction -> 18 F TD, ~50-65% RH. A smaller TD needs more coil. The coil rating at the design TD governs.

Formula or tableDTD = box_temp - saturated_suction_temp; humidity band by DTD (Heatcraft classes: 7-9 F ~90% RH, 10-12 F ~80-85%, 12-16 F ~65-80%, 17-22 F ~50-65%).

Source and editionThe evaporator design temperature difference (DTD) and the resulting box-humidity bands, from refrigeration coil-selection practice, by name.

Free accessThe DTD-to-humidity relationship is standard published refrigeration coil-selection guidance.

What governsEstimate. AHJ and licensed professional govern.

API field namesbox_temp_f, sst_f, dtd