Walk-In Cooler Heat Load

Box load = transmission (U x area x deltaT) + infiltration + product + internal, times a safety factor.

Run the calculator

Example

You enter

You get

Checked against published worked examples from: Heatcraft Refrigeration Products.

Details, formula, and sources

ScopeU 0.05, 800 ft^2, 60 F, +3000/5000/1500, 1.10 -> 2,400 transmission, 13,090 Btu/hr (1.09 tons); a 6 in panel (U 0.03) cuts it to 12,034. That is a 24-hr average: the equipment removes it in 16 hr (no defrost timer) or 18 hr (timer), so 13,090 x 24/16 = 19,635 Btu/hr of equipment. The box-load method and equipment ratings govern.

Formula or tabletransmission = U x area x deltaT; total = (transmission + infiltration + product + internal) x safety; tons = total / 12000.

Source and editionThe walk-in cooler/freezer box heat-load method (transmission + infiltration + product + internal, with a safety factor), from ASHRAE Refrigeration, by name.

Free accessThe four-component box-load method is standard published refrigeration practice; the ASHRAE Handbook - Refrigeration covers it.

What governsEstimate. AHJ and licensed professional govern.

API field namesu_factor, area_ft2, delta_t_f, infiltration_btuh, product_btuh, internal_btuh, safety, transmission_btuh, total_btuh