Hydronic Expansion Tank
Required diaphragm tank volume from system volume, fill, and relief pressures.
Example
You enter
- System water volume (gal) 100
- Fill temp (°F) 60
- Max water temp (°F) 200
- Fill pressure (psi) 12
- Relief pressure (psi) 30
You get
- Required tank volume 9.25 gal
- Pre-charge (set air side) 12 psi
Details, formula, and sources
V_tank = V_sys × ((ρ_cold / ρ_hot) − 1) / (1 − P_initial_abs / P_final_abs). Absolute pressures (gauge + 14.7 psi); densities from a public water-density table.
ASHRAE Handbook (HVAC Systems and Equipment) by name; water-density table from NIST.
NIST data free at nist.gov; ASHRAE Handbook licensed.
Estimate. AHJ and licensed plumber / gas fitter govern. Verify against the IPC / IFGC edition adopted in your jurisdiction.
Field names used by the API: system_volume_gal, fill_temperature_F, max_temperature_F, fill_pressure_psi, relief_pressure_psi, tank_volume_gal, precharge_psi
- Working temperatures user-supplied (cold fill, hot operating)user input
- Final pressure margin set 5 psi below relief-valve settingASHRAE Handbook by name