Filter Pressure Drop and Fan-Energy Penalty

Clean and change-out pressure drop by MERV / HEPA class (velocity-scaled, user-overridable cut-sheet defaults).

Run the calculator

Example

You enter

You get

Details, formula, and sources

The fan power at each via brake-HP, and the annual fan energy and loading penalty over a clean filter. Per ASHRAE 52.2-2017 and first-principles fan power.

Airflow (CFM) = face area × face velocity. Pressure drop scales ~linearly with face velocity (Darcy regime): dp(V) = dp_ref × V / 300 fpm. Fan power (kW) = (CFM × dp_in_wc / 6356) / fan total efficiency × 0.7457. Average drop over a linear loading cycle = (clean + change-out) / 2; annual fan energy = average-drop kW × runtime; loading penalty = (average − clean) kW × runtime.

ASHRAE 52.2-2017 (Method of Testing General Ventilation Air-Cleaning Devices for Removal Efficiency by Particle Size) by name; manufacturer published cut sheets for the pressure-drop values.

ASHRAE 52.2 TOC free at ashrae.org; full standard licensed; manufacturer cut sheets free at each vendor site.

Estimate. AHJ and licensed mechanical contractor govern. ACCA Manual J / D / S supersede rules of thumb.

Field names used by the API: filter_type, face_area_ft2, face_velocity_fpm, fan_total_efficiency, runtime_hr_per_year, airflow_cfm, clean_dp_in_wc, final_dp_in_wc, clean_fan_kw