Hydrant Rated Flow at 20 psi (NFPA 291)

Hydrant rated capacity at 20 psi residual.

Run the calculator

Example

You enter

You get

Checked against published worked examples from: City of Temecula Fire Prevention Bureau.

Details, formula, and sources

ScopeQR = QF (hr/hf)^0.54, hf = static - residual, hr = static - 20, with the AA/A/B/C color class. Static 70, residual 50, QF 1000 gpm -> 1640 gpm, Class AA; static 65, residual 45, QF 800 -> 1240 gpm, Class A. A field/planning estimate; the water authority's data govern.

Formula or tablehf = static - residual; hr = static - 20; QR = QF (hr/hf)^0.54; class AA/A/B/C by QR.

Source and editionThe NFPA 291 hydrant rated-flow-at-20-psi projection and the color-class marking, by name.

Free accessThe QR = QF (hr/hf)^0.54 flow projection and the AA/A/B/C color classes are the published NFPA 291 method.

What governsEstimate. AHJ and licensed professional govern.

API field namesstatic_psi, residual_psi, qf_gpm, qr_gpm