Hydronic Buffer Tank Sizing (Anti-Short-Cycle)

Buffer-tank volume to stop a boiler or chiller short-cycling.

Run the calculator

Example

You enter

You get

Details, formula, and sources

V = on-time x (source min - zone load) / (500 x delta_T). The worst case is at nearly zero load, when the full minimum output has nowhere to go but the tank -- sizing at the design load badly undersizes it. The same formula sizes a chiller buffer. A sizing aid, not the manufacturer's data.

V_gal = min_on_time_min x (source_min_btu - zone_min_load_btu) / (500 x delta_t_f); no buffer when the zone load meets or exceeds the source minimum.

ASHRAE / Idronics (Caleffi) anti-short-cycle buffer-tank practice, by name.

The buffer-tank sizing relation is standard hydronic design practice; the equipment minimum-cycle data and the manufacturer govern.

Estimate. AHJ and licensed professional govern.

Field names used by the API: min_on_time_min, source_min_btu, delta_t_f, buffer_volume_gal