Isolator Static Deflection for a Target Isolation

Enter the running speed and the isolation efficiency you want, get the static deflection to specify for the mount.

Run the calculator

Example

You enter

You get

Details, formula, and sources

From T = 1 - efficiency, ratio = sqrt(1 + 1/T), fn = (rpm/60)/ratio, and deflection = (3.13/fn)^2 in. 90% isolation of a 900 rpm fan needs 0.48 in of deflection (a 4.5 Hz mount); tighten to 95% and it nearly doubles to 0.91 in - the softer the mount, the better the isolation, and this says how soft. Feeds straight back into the forward calculation. Undamped single-DOF; the isolator selection and the mechanical engineer govern.

T = 1 - efficiency/100; ratio = sqrt(1 + 1/T) (> sqrt(2)); fn = (rpm/60)/ratio Hz; deflection = (3.13/fn)^2 in.

ASHRAE Handbook -- Fundamentals, Sound and Vibration chapter, the single-degree-of-freedom vibration isolator (the classical Den Hartog transmissibility relation) solved for the required static deflection, by name.

The single-DOF isolator relations are standard vibration theory published in the ASHRAE Handbook -- Fundamentals and every mechanical-vibration text; inverting them for the deflection is public arithmetic.

Estimate. AHJ and licensed professional govern.

Field names used by the API: equipment_rpm, target_efficiency, deflection_in, fn_hz, ratio