Isolator Static Deflection for a Target Isolation

Enter the running speed and the isolation efficiency you want, get the static deflection to specify for the mount.

Run the calculator

Example

You enter

You get

Checked against published worked examples from: Barry Controls (Hutchinson).

Details, formula, and sources

ScopeFrom T = 1 - efficiency, ratio = sqrt(1 + 1/T), fn = (rpm/60)/ratio, and deflection = (3.13/fn)^2 in. 90% isolation of a 900 rpm fan needs 0.48 in of deflection (a 4.5 Hz mount); tighten to 95% and it nearly doubles to 0.91 in - the softer the mount, the better the isolation, and this says how soft. Feeds straight back into the forward calculation. Undamped single-DOF; the isolator selection and the mechanical engineer govern.

Formula or tableT = 1 - efficiency/100; ratio = sqrt(1 + 1/T) (> sqrt(2)); fn = (rpm/60)/ratio Hz; deflection = (3.13/fn)^2 in.

Source and editionASHRAE Handbook -- Fundamentals, Sound and Vibration chapter, the single-degree-of-freedom vibration isolator (the classical Den Hartog transmissibility relation) solved for the required static deflection, by name.

Free accessThe single-DOF isolator relations are standard vibration theory published in the ASHRAE Handbook -- Fundamentals and every mechanical-vibration text; inverting them for the deflection is public arithmetic.

What governsEstimate. AHJ and licensed professional govern.

API field namesequipment_rpm, target_efficiency, deflection_in, fn_hz, ratio