Neutral Grounding Resistor Sizing (IEEE 142)

Sizing the NGR off line-to-neutral, not line-to-line: a resistance-grounded transformer neutral limits a ground fault to a known current -- a few amps (HRG, keep running through the first fault) or 100-400 A (LRG, fast tripping). The resistor sees V_LN = V_LL / sqrt(3), NOT V_LL, so sizing off V_LL makes it sqrt(3) too large and the fault too small to sense. R = V_LN / I_ground; P = I^2 R = V_LN x I. A 480 V system at a 5 A HRG target: the resistor sees 277 V -> 55.4 ohm, 1,386 W continuous. HRG resistors are rated continuous, LRG for the short trip time. A design aid; IEEE 142 and the protection scheme govern.

Run the calculator

Formula and source

V_LN = V_LL / sqrt(3); R = V_LN / I_ground; P = I_ground^2 x R (= V_LN x I_ground).

Neutral grounding resistor sizing (IEEE 142 grounding practice), first-principles, by name; IEEE 142 and the protection scheme govern.

Audience

This tile is built for electricians and the adjacent professions in the Electrical group. The interactive calculator runs entirely in your browser. No account, no fee, no advertising, no tracking.

Related tools

Posture

Rough Logic answers the math question the working professional asks on the job. The site is a calm, fast, ad-free, account-free, ever-free reference. It does not interpret code. It does not replace the licensed professional. It does not store your inputs. The Authority Having Jurisdiction governs all installations and inspections.